Powervar ABC15.0-20D40Y Series 2000 GPI Global Power Interface
- Make Powervar
- Hertz 50Hz/60Hz
- Model ABC15.0-20D40Y
- Serial 74015-54R
- Weight 571
- Voltage 120V/220V
- Working Working
- Warranty 30-Day Warranty, 100% Parts and Labor
- Dimensions 36×30×30 in
- Shipping Type Freight
- Item Condition Pre-owned
-
The Powervar Global Power Interface (GPI) Series 2000 Power Conditioners incorporate a low impedance isolation transformer, as well as a surge diverter and power line filter to eliminate noise, spikes, and transients before they have a chance to wreak havoc on your equipment. Voltage distribution and conditioning all in one solution. Standard equipment includes safety interlocks, emergency machine off (EMO), casters, and lockout/tagout breaker. EMO, safety interlocks, lockout/tagout breaker, and casters are standard on all models.
Specifications
- Model ABC15.0-XXD20Y
- Input Voltage 208/240/480/600 delta connection (4 wire)
- Output Voltage 208/120 wye (5 wire)
- Frequency 60 Hz. only
- Continuous Capacity 15 kVA
- BTU/Hr. Output 1536
- Efficiency > 97% (at full load, unity power factor)
- Step Load Change + 0.8% (at unity power factor)
- Noise Rejection With unit under power and the isolation transformer configured for a transformation
- ratio of 1:1 and with an ANSI/IEEE C62.41, Category A pulse applied either normal mode
or common mode at the input, the noise output voltage will be less than 10 volts normal
mode and less than .5 volts (½ of one volt) common mode in all four quadrants
(CM-NM, NM-NM, CM-CM, NM-CM). - Surge Voltage Withstand Tested under power to ANSI/IEEE C62.41, Category A & B (formerly IEEE587-1980).
- Power conditioner tested to withstand up to 6000 volts @ 3000 amp ringwave and unipo
lar impulse. - Construction Materials Transformer wires are copper and insulated with Class H materials.
- Windings are insulated with Nomex paper insulation before vacuum varnishing. Internal wiring is a mini.
- mum of 200 degree C rated and sleeved with Class H materials. Grain oriented
- silicon iron cores are constructed using 14 mil. laminations interleaved one to one. Eddy
- currents are minimized and external magnetic fields are below 0.1 oersted (at 12 inches
distance in any direction). - Unit is RoHS compliant.
- Model ABC15.0-XXD20Y
Testimonials
“REUZEit has been a great partner for our used equipment needs and always provide timely updates of new arrivals of consigned equipment.”
“Great company to work with. Tammy completed our first international equipment shipment with ease.”
“Fast response, open to adjusting schedule as needed, and great customer interaction.”